# Assessing HVAC airflow modulation strategies to reduce short-term aerosol transmission in office environments

**Authors:** Mina A. Saad, Amr Hassan, Ahmed Hanafy, Mahmoud Salem, Micheal William

PMC · DOI: 10.1038/s41598-025-08394-4 · Scientific Reports · 2025-07-04

## TL;DR

This study shows how placing HVAC exhaust diffusers above a cough source can reduce short-term aerosol spread in offices.

## Contribution

The study introduces a CFD-based analysis of diffuser placement effects on early-phase aerosol dispersion.

## Key findings

- Exhaust diffusers above the cough source reduce lateral particle spread by 40%.
- Maintaining a two-meter distance reduces particle concentration by 82–89%.
- Conventional layouts fail to control short-term lateral spread despite reducing overall particle mass.

## Abstract

Airborne transmission of respiratory pathogens in indoor environments remains a significant global health challenge. While existing research broadly addresses ventilation effectiveness, there is a critical need to understand how specific diffuser placements influence early-phase aerosol dispersion immediately following a cough event. This study uses Computational Fluid Dynamics (CFD) with an Eulerian–Lagrangian approach and the Discrete Phase Model to analyze initial droplet transport, evaporation, and nuclei concentration under different air distribution configurations. The results demonstrate that conventional parallel exhaust configurations, though effective at reducing overall particle mass, can fail to control the lateral spread of infectious nuclei in the short term. In contrast, placing exhaust diffusers above the cough source reduces the lateral particle spread by approximately 40% compared to conventional layouts. Additionally, maintaining the WHO-recommended two-meter distance results in an 82–89% reduction in particle number concentration during the early dispersion phase. These findings underscore the importance of diffuser placement for controlling short-term particle dispersion immediately after a cough event in mechanically ventilated office environments. The study’s scope is limited to early-phase dispersion dynamics within a 10-second simulation period, and further research is needed to assess long-term aerosol suspension, removal mechanisms, and infection risk. Nonetheless, the results offer practical insights for HVAC design and support the integration of ventilation strategies with physical distancing measures to reduce near-field exposure risks.

## Full-text entities

- **Diseases:** infection (MESH:D007239), respiratory (MESH:D012131), cough (MESH:D003371)

## Full text

_Full body text omitted from this summary view._ Fetch the complete paper as Markdown: https://tomesphere.com/paper/PMC12227705/full.md

## Figures

17 figures with captions in the complete paper: https://tomesphere.com/paper/PMC12227705/full.md

## References

7 references — full list in the complete paper: https://tomesphere.com/paper/PMC12227705/full.md

---
Source: https://tomesphere.com/paper/PMC12227705