# Employing Eye Trackers to Reduce Nuisance Alarms

**Authors:** Katherine Herdt, Michael Hildebrandt, Katya LeBlanc, Nathan Lau

PMC · DOI: 10.3390/s25092635 · Sensors (Basel, Switzerland) · 2025-04-22

## TL;DR

This study explores using eye trackers to reduce nuisance alarms by adjusting their salience based on operator gaze behavior, but found no significant improvement in task performance.

## Contribution

The study introduces three gaze-based alarm acknowledgment methods to infer operator anticipation and reduce alarm salience.

## Key findings

- No significant improvement in control task performance was observed with gaze-based alarm methods.
- Scenario type influenced which gaze-based alarm method was more frequently used.
- Participants preferred gaze-based alarm methods over standard alarm design.

## Abstract

When process operators anticipate an alarm prior to its annunciation, that alarm loses information value and becomes a nuisance. This study investigated using eye trackers to measure and adjust the salience of alarms with three methods of gaze-based acknowledgement (GBA) of alarms that estimate operator anticipation. When these methods detected possible alarm anticipation, the alarm’s audio and visual salience was reduced. A total of 24 engineering students (male = 14, female = 10) aged between 18 and 45 were recruited to predict alarms and control a process parameter in three scenario types (parameter near threshold, trending, or fluctuating). The study evaluated whether behaviors of the monitored parameter affected how frequently the three GBA methods were utilized and whether reducing alarm salience improved control task performance. The results did not show significant task improvement with any GBA methods (F(3,69) = 1.357, p = 0.263, partial η2 = 0.056). However, the scenario type affected which GBA method was more utilized (X2 (2, N = 432) = 30.147, p < 0.001). Alarm prediction hits with gaze-based acknowledgements coincided more frequently than alarm prediction hits without gaze-based acknowledgements (X2 (1, N = 432) = 23.802, p < 0.001, OR = 3.877, 95% CI 2.25–6.68, p < 0.05). Participant ratings indicated an overall preference for the three GBA methods over a standard alarm design (F(3,63) = 3.745, p = 0.015, partial η2 = 0.151). This study provides empirical evidence for the potential of eye tracking in alarm management but highlights the need for additional research to increase validity for inferring alarm anticipation.

## Full-text entities

- **Diseases:** Alarms (MESH:D051270)
- **Species:** Homo sapiens (human, species) [taxon 9606]

## Full text

_Full body text omitted from this summary view._ Fetch the complete paper as Markdown: https://tomesphere.com/paper/PMC12074377/full.md

## Figures

1 figure with captions in the complete paper: https://tomesphere.com/paper/PMC12074377/full.md

## References

103 references — full list in the complete paper: https://tomesphere.com/paper/PMC12074377/full.md

---
Source: https://tomesphere.com/paper/PMC12074377